EAN: 3760244880932 SKU ALE244810 Categories , , Tags , ,

UNIVERSAL : 198 to 440 V main input voltage.
POWERFUL : to cumulate n+1(Parallel active mode).
REDUNDANT : integrated function – without option
SPACE SAVING – WIRING SAVINGS
DIAGNOSIS : Alarm by Relay with invert contact.
EFFICIENCY : >90% (cost and energy saving)
ACTIF power corrector (PFC).
PROTECTED : against short circuit.
EASY : Direct DIN rail mounting.
Double plugable terminal blocks at the output.
POWER BOOST : Delivers 20% more current for one second

Download documentationDownload the quick user manualDownload the detailed user manual

280,00  HT

DIN RAIL regulated switching power supply : 24V or 48V 300W ; Primary198-440V ; Power-Boost

EAN: 3760244880932 Ref. : ALE244810 Categories , , Tags , ,

UNIVERSAL : 198 to 440 V main input voltage.
POWERFUL : to cumulate n+1(Parallel active mode).
REDUNDANT : integrated function – without option
SPACE SAVING – WIRING SAVINGS
DIAGNOSIS : Alarm by Relay with invert contact.
EFFICIENCY : >90% (cost and energy saving)
ACTIF power corrector (PFC).
PROTECTED : against short circuit.
EASY : Direct DIN rail mounting.
Double plugable terminal blocks at the output.
POWER BOOST : Delivers 20% more current for one second

Download documentationDownload the quick user manualDownload the detailed user manual

280,00  HT

Description

Voltage
• Floating outputs on double pluggable terminal blocks
• Maximum wire section : 2,5mm² (AWG12).
• Output voltage : configurable 24 V (Adj. 23,5 to 28,6 V) or 48 V (Adj. 47 to 57,2 V).
• Regulation : < 10 mV for a load variation from 10 to 90%.
<5 mV for a line variation from 198 to 440 V.
• Ripple : < 10 mV rms including :
<10 mV peak to peak of the signal at 100 kHz
<60 mV peak to peak of switching spikes
• Hold-up time : 25 ms at half load and 18 ms at full load (198V line input).
• Indicator : green power-on LED indicator.
yellow LED “selection of the output voltage”.
• Information relay : Invert contact, 120 VAC (30 VDC) 1 A on plug-in terminal block for 1.3 mm² wires (AWG16)

Current
• Max I : 24 V -> 11,5 A in short-circuit condition.
10A at 24 V ; 8,6 A at 28 V.
: 48 V -> 5,75 A in short-circuit condition.
5 A at 48 V ; 4,3 A at 56 V.
Power
• Constant output power : 240 W.

Protections
• Against short circuits by current limit.
• Against primary circuit overcurrent, by internal fuse.
• Against output overload by disruption.
• Safety : Complies with EN 61010-1, EN61010-2-201 and EN 62368-1.
• EMC : Complies with EN 61000-3-2, EN 61000-6-2 and EN 61000-6-4.
• Insulation Class : I.
• Overvoltage Category : II ; Pollution Degree : 2.
• Installation altitude : < 2000 m.
• Protection level : IP 20.
• Operating temperature : -25 to +70 °C, derating 6W/°C from 50°C.
• Input voltage : 220-400 VAC (198 to 440 Volts), 50-60 Hz.
• Mains input : 3-pin plug-in terminal block for 2,5 mm² (AWG 12) wire.
• Power consumption : 270 W max.
• Power factor : built with PFC.
• Dielectric strength : 4500 VAC between input and output.
2500VAC between input to chassis.
• Presentation : metal case with screen printed front panel.
• Mounting : Integral symmetrical DIN rail clips.

Paralleling / Redundant
• Load share controller (1 wire) on dual spring pluggable terminal blocks with for 1,3 mm² wire (AWG 16).
• Redundant mode (n+1) include with OR-ing

Additional information

Nombre de voie

1 channel

Puissance

240 WATTS

Volts

24 V, 48 V

Ampères

10 A, 5 A

Regulations

• Safety : Complies with EN 61010-1, EN61010-2-201 and EN 62368-1.
• EMC : Complies with EN 61000-3-2, EN 61000-6-2 and EN 61000-6-4.
• Insulation Class : I.
• Overvoltage Category : II ; Pollution Degree : 2.
• Installation altitude : < 2000 m.
• Protection level : IP 20.