UNIVERSAL : direct operation for 12 or 24 V system
CONTROL : state of faults on relay status
PRACTICAL : batterie charge current adjustable from 0,3 to 2 A
Toggle push of release the ” by-pass ” system
FASTER : screw terminal blocks
PROTECTED : against short-circuits in the mains & battery polarity inversion
EASY : direct DIN rail or panel mounting
INTELLIGENT : Preponderance to start, on AC input or battery

Download documentationDownload the user manual

75,00  HT

Back up system 12 or 24V until 20AH

UNIVERSAL : direct operation for 12 or 24 V system
CONTROL : state of faults on relay status
PRACTICAL : batterie charge current adjustable from 0,3 to 2 A
Toggle push of release the ” by-pass ” system
FASTER : screw terminal blocks
PROTECTED : against short-circuits in the mains & battery polarity inversion
EASY : direct DIN rail or panel mounting
INTELLIGENT : Preponderance to start, on AC input or battery

Download documentationDownload the user manual

75,00  HT

Description

12 or 24 V auto configuration.
• For operation with lead-acid batteries
• Connexion on disconnect screw terminal block for 2,5mm2 wires (AWG12).

Fonctions
INDICATOR RELAY STATUS
Sector absence                     Led Jaune         1 RT 250 V~1 A
Battery charge fault            Led Jaune         1 RT 250 V~1 A
Output voltage presence    Led Verte
Inverse battery                     Led Rouge

Sector supervision
• Inputs on disconnect screw terminal block for 2,5 mm2 wires (AWG12).
• Input voltage : 230 V ±10%. Power consumption : 0,2 W
• Detection : by coupler and automatic switch without power cut.

Battery supervision
• Supervision system of status and current charge of the battery
• Discharge limiter system (DLS) : disjonction at 90% voltage rms
• Monitoring : ” by-pass ” push toggle to start only on battery.

Protection
• Against overcurrent or short-circuits in the primary by 10A fuse
• Against voltage inversion by électronic protection and by fuse

Other specifications
• Safety : Class II, Complies with EN 61010-1, EN 61010-2-201 and § A4-A6 of the standard NF S 61-940
• EMC : Complies with EN 61000-6-2, and EN 61000-6-4
• Overvoltage Category : II ; Pollution Degree : 2.
• Installation altitude : < 2000 m.
• Protection level : IP30
• Operating temperature : +5°C to +50°C
• Power consumption : 150 mA
• Dielectric strength : 2500 VAC from input to output
• Presentation modular polycarbonate case (3 modules) screenprinted
• Dimension : 54 x 95 x 58 mm (lxhxp)
• Mounting : Case integrated clips for symetrical DIN rails 35×7,5 mm or 35×15 mm.
Case removable wall mounting clips for 4 mm screws

Additional information

Nombre de voie

1 channel

Volts

12 V, 24 V

Ampères

0 – 10 A

Regulations

• Safety : Class II, Complies with EN 61010-1, EN 61010-2-201 and § A4-A6 of the standard NF S 61-940
• EMC : Complies with EN 61000-6-2, and EN 61000-6-4
• Overvoltage Category : II ; Pollution Degree : 2.
• Installation altitude : < 2000 m.
• Protection level : IP30