EAN: 3760244880321 SKU ALE2412 Categories ,

PRECISE : Output ripple < 3 mV rms.
COMPLIE : EN 61000-3-2 Built in actif power corrector (PFC).
DIAGNOSTIS : Alarm by Relay with invert contact.
PRACTICAL : Output voltage adjustable from 20 to 30 V.
UNIVERSAL : 198 to 440 V main input voltage.
POWERFUL : to cumulate n+1(Parallel active mode).
PROTECTED : against short circuit.
EASY : Direct DIN rail mounting – Spring terminal block

Download documentationDownload the user manual

245,00  HT

DIN RAIL regulated switching power supply : 24V (Adj. 20 to 30V) ; 300W ; Primary 190-440V

EAN: 3760244880321 Ref. : ALE2412 Categories ,

PRECISE : Output ripple < 3 mV rms.
COMPLIE : EN 61000-3-2 Built in actif power corrector (PFC).
DIAGNOSTIS : Alarm by Relay with invert contact.
PRACTICAL : Output voltage adjustable from 20 to 30 V.
UNIVERSAL : 198 to 440 V main input voltage.
POWERFUL : to cumulate n+1(Parallel active mode).
PROTECTED : against short circuit.
EASY : Direct DIN rail mounting – Spring terminal block

Download documentationDownload the user manual

245,00  HT

Description

Voltage 
Floating outputs on dual spring terminal blocks with levers for 2,5 mm² (AWG 12) wire.
• Output voltage : adjustable from 20 to 30 V.
• Regulation : < 10 mV for a load variation from 0 to 100%.
< 5 mV for a line variation from 198 to 440 V.
• Ripple : < 3 mV rms including :
< 8 mV peak to peak of the signal at 100 kHz
< 5 mV peak to peak of the signal at 100 Hz
< 40 mV peak to peak of switching spikes
• Internal resistance : < 1 m Ω
• Hold-up time : 25 ms at half load and 12 ms at full load (198 V line input).
• Indicator : green power-on LED indicator.
overheat or overvoltage red LED indicator.
• Information Relay : Invert contact, 250 VAC (30 VDC) 1 A.

Current
• Max I : 15,5 A in short circuit condition.
15 A at 20 V, 12,5 A at 24 V, 10 A at 30 V.

Power
• Max output power : 300 W from 20 to 30 V.

Protections
• Against short circuits by current limit.
• Against primary circuit overcurrent, by internal fuse.
• Against output overload by voltage limiting to 33 V.
• Against current reverse power surges on the output, by fuse.

Other specifications
• Safety : Complies with EN 61010-1, EN61010-2-201 and EN 62368-1.
• EMC : Complies with EN 61000-6-2 and EN 61000-6-4.
• Insulation Class : I.
• Overvoltage Category : II ; Pollution Degree : 2.
• Installation altitude : < 2000 m.
• Protection level : IP 30.
• Operating temperature : +5 to +50 °C.
• Input voltage : 220-400 VAC (198 to 440 Volts), 50-60 Hz.
• Mains input : Dual spring terminal blocks for 1,5 mm² (AWG 16) wire.
• Power consumption : 360 W max.
• Power factor : 0,99 (built with PFC).
• Dielectric strength : 4000 VAC between input and output.
2500 VAC between input to chassis.
• Presentation : galvanized steel case and front panel with epoxy finish.
• Mounting : Integral symmetrical DIN rail clips.

Paralleling
• Load share controller (1 wire) on dual spring terminal blocks with level for 1,5 mm² wire (AWG 16).

Additional information

Nombre de voie

1 channel

Puissance

300 WATTS

Volts

24 V, 24 V (Adj 20 to 30 V), 27,2 V, PRIM. 230 V, PRIM. 400 V

Ampères

12,5 A

Regulations

• Safety : Complies with EN 61010-1, EN61010-2-201 and EN 62368-1.
• EMC : Complies with EN 61000-6-2 and EN 61000-6-4.
• Insulation Class : I.
• Overvoltage Category : II ; Pollution Degree : 2.
• Installation altitude : < 2000 m.
• Protection level : IP 30.