Description
Voltage
• Floating outputs on spring terminal block with levers for 2,5 mm2 (AWG12) wires.
• Output voltage :adjustable from 5 to 29 V by 12 position switch, and fine adjustment
switch positions : 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28 Volts.
Fine adjustment range : ± 1 Volt, whatever the switch setting
12 and 24 V lead-acid battery charger positions identified by two LED indicators.
• Regulation :
< 30 mV at 5 V and < 10 mV at 29 V for a load variation from 0 to 100%.
< 1 mV at 29 V @ 2,1 A and < 4 mV at 5 V @ 4 A for ±10% line variation.
• Dynamic regul. :
< 1% to 29V and < 5% to 5 V for a load change from 10 to 90%.
• Ripple : < 3 mV rms including :
< 3 mV peak to peak of the 100 kHz signal
< 4 mV peak to peak of the 100 Hz signal
< 10 mV peak to peak of switching transients
• Hold-up time : 25 ms at half load and 12 ms at full load. (190 V line input)
• Indicators : Green LED indicator : “power supply operating”
Yellow LEDs indicator : “12 V and 24 V battery charger position”
Red LED indicator : “status, output fuse broken” or “overheat”
The yellow LEDs also indicate battery-backed operation.
Current
• Max I : 4,2 A in short circuit condition
4 A to 5 V, 3,5 A to 12 V, 2,5 A to 24 V and 2,1 A to 29 V
Battery charger
• Rated capacity of the lead-acid batteries with elctrolyte free :
35 Ah for 12 V and 20 Ah for 24 V.
• Minimum capacity of the lead-acid batteries sealed :
10 Ah for 12 V and 7 Ah for the 24 V.
(In all the cases, to refer to the note of the batteries manufacturer)
Remote sensing
• Correction of the voltage drop in the wires (4 wires method)
• Input on disconnect scribe terminal blocks for 2,5mm2 wires (AWG12)
• Correction : Max 3 V (1,5 V per wire)
• Ripple : < 30 mV for a load variation from 0 to max.
Power
• A linear function of voltage from 60 W to 20 W (29 to 5 Volts).
Protection
• Against short circuit, by current limit.
• Against overcurrent on primary circuit, by fuse.
• Battery reverse polarity protection by output fuse.
• Against overtemperature, by thermal shutdown.
• Cover on input output terminal block
Other specifications
• Safety : Class II, Safety Extra Low Voltage (SELV), complies with EN 61010-1, EN 61010-2-201 and EN 62368-1.
• EMC : Complies with EN 61000-6-2 and EN 61000-6-4.
• Overvoltage Category :II ; Pollution Degree : 2.
• Installation altitude :< 2000 m.
• Protection level : IP 30.
• Operating temperature:from -25 to +60 °C ; derating : 1 W/°C from +40 °C
• Input voltage : 220-240 VAC (190 to 264 Volts), 50-60 Hz.
• Mains input : spring terminal block with levers for 2,5 mm², (AWG 12) wires.
• Power consumption : 71 W max.
• Dielectric strength : 3000 VAC from input to output.
• Presentation : modular polycarbonate case (6 x 17.5 mm) screenprinted.
• Mounting : Clips package integrated in modular case for DIN rails profile 35×7,5 mm or 35×15 mm.
Removable wall mouting integrated to the case for 4mm screws