EAN: 3760244880246 SKU ALE1202 Categories , Tag

PRECISE : Output ripple < 3 mV rms.
– Remote sensing to overcome voltage drop in the power lines.
PRACTICAL : Output voltage adjustable from 10 to 15 V.
– Spring terminal block.
PROTECTED : Short circuit protection.
EASY : Direct DIN rail or panel mounting.

Download documentationDownload the user manual

53,00  HT

DIN RAIL regulated switching power supply : 12V (Adj. 10 to 15V) ; 30W

EAN: 3760244880246 Ref. : ALE1202 Categories , Tag

PRECISE : Output ripple < 3 mV rms.
– Remote sensing to overcome voltage drop in the power lines.
PRACTICAL : Output voltage adjustable from 10 to 15 V.
– Spring terminal block.
PROTECTED : Short circuit protection.
EASY : Direct DIN rail or panel mounting.

Download documentationDownload the user manual

53,00  HT

Description

Voltage
• Floating outputs on spring terminal block for 2,5 mm2 (AWG12) wires
• Output voltage : adujustable from 10 to 15 V.
• Regulation : <25 mV for a load variation from 0 to 100% 5 mV for a line variation from -10 to +10%
• Ripple : < 3 mV rms including :
3 mV peak to peak of the signal at 65 kHz
< 4 mV peak to peak of the signal at 100 Hz
< 35 mV peak to peak of switching spikes
• Hold-up time : 50 ms at full load (230 V line input)
• Indicator : green power-on LED indicator

Current
• Max I : 3 A at 10 V
2,5 A at 12 V
2 A at 15 V

Power
• Max output power : 30 W

Protections
• Against short-circuits by circuit breaker with automatic reset
• Against transients on the primary circuit by varistor
• Against overcurrent on primary circuit by fuse

Remote sensing
• Correction of the voltage drop in the wires (4 wires method)
• Input on disconnect scribe terminal blocks for 2,5 mm2 wires (AWG12)
• Correction : Max 3 V (1,5 V per wire)
• Ripple : < 30 mV for a load variation from 0 to max.

Other specifications
• Safety : Class II, Safety Extra Low Voltage (SELV), complies with EN 61010-1, EN 61010-2-201 and EN 61368-1.
• EMC : Complies with EN 61000-6-2 and EN 61000-6-4.
• Overvoltage Category : II ; Pollution Degree : 2.
• Installation altitude : < 2000 m.
• Protection level : IP30
• Operating temperature : from -25 °C to +70 °C, Derating : 1 W/°C from. +55 °C
• Input voltage : 190 to 264 V, 50-60 Hz
• Mains input : disconnect scribe terminal blocks for 2,5 mm² wires (AWG12)
• Power consumption : max 35 W
• Dielectric strength : 3000 VAC from input to output
• Presentation : polycarbonate modular case (3 modules) screenprinted
• Dimension : 54 x 95 x 58 mm (lxhxp)
• Mounting : Clipspackage integrated in modular case for DIN rail profile 35×7,5 mm or 35×15 mm
removable wall mounting integrated case to the 4 mm screws.

Additional information

Nombre de voie

1 channel

Puissance

30 WATTS

Volts

12 V, 12 V (Aj 10 à 15 V), 13,6 V, PRIM. 230 V

Ampères

2,5 A

Regulations

• Safety : Class II, Safety Extra Low Voltage (SELV),                                    complies with EN 61010-1, EN 61010-2-201 and EN 61368-1.
• EMC : Complies with EN 61000-6-2 and EN 61000-6-4.
• Overvoltage Category : II ; Pollution Degree : 2.
• Installation altitude : < 2000 m.
• Protection level : IP30