Description
Voltage
• Floating outputs on screw terminal block for 2,5 mm² rigid or 1,5 mm² flexible wire.
• Output voltage : 24 Volts (set).
• Accuracy : ± 0,5%.
• Regulation : < 40 mV for a load variation from 0 to 100%.
< 10 mV for a 10% line variation.
• Ripple : < 3 mV peak to peak or 1 mV rms.
• Internal resistance : < 50 mΩ.
• Hold-up time : 20 ms at half load and 5 ms at full load.
• Indicator : power-on LED indicator.
Current
• Max I : 0,8 A.
• Idc : 2 A (allows current surges).
Protection
• Against short circuit, by current limit.
• Against overtemperature, by thermal shutdown.
• Against overcurrent on transformer primary, by fuse
Other specifications
• Safety : Class I, complies with EN 61010-1 and EN 61010-2-201 overvoltage category II, pollution degree 2.
Built-in transformer as per EN 61558-2-6.
• EMC : Complies with EN 61000-6-2 and EN 61000-6-4.
• Installation altitude : < 2000 m.
• Input voltage : 400 Volts, ± 10%, 50/60 Hz.
• Mains input : screw terminal block for 2,5 mm² rigid or 1,5 mm² flexible wire.
• Power consumption : 50 VA max.
• Dielectric strength : 5550 VAC from input to output,
3250 VAC from input to chassis.
• Insulation resistance : 100 MΩ/1000 V from output to chassis.
• Presentation : Galvanized base with lugs and clips for symmetrical DIN rail mounting.
• Optional : Protective cover, reference: CP 910A
Mounting
• 3 through slots (4,5 x 9 mm) for M4 screws, or 2 symmetrical DIN rail mounting clips (fitted).