Description
Voltage
• Floating outputs on dual spring terminal blocks with levers for 2,5 mm² (AWG 12) wire.
• Output voltage : adjustable from 10 to 15 V.
• Regulation : < 40 mV for a load variation from 0 to 100%.
< 5 mV for a line variation from 198 to 440 V.
• Ripple : < 3 mV rms including :
< 8 mV peak to peak of the signal at 100 kHz
< 5 mV peak to peak of the signal at 100 Hz
< 40 mV peak to peak of switching spikes
• Internal resistance : < 2 mΩ
• Hold-up time : 25 ms at half load and 12 ms at full load (198 V line input).
• Indicator : green power-on LED indicator.
overheat or overvoltage red LED indicator.
• Information Relay : Invert contact, 250 VAC (30 VDC) 1 A.
Current
• Max I : 25,5 A in short circuit condition.
25 A from 10 to 12 V, 20 A 15 V
Power
• Max output power : 300 W from 12 to 15 V, 250 W at 10 V.
Protections
• Against short circuits by current limit.
• Against overcurrent on primary circuit by internal fuse.
• Against output overload by voltage limiting to 17 V.
• Against current reverse power surges on the output, by fuse
Other specifications
• Safety : Complies with EN 61010-1, EN61010-2-201 and EN 62368-1.
• EMC : Complies with EN 61000-6-2 and EN 61000-6-4.
• Insulation Class : I.
• Overvoltage Category : II ; Pollution Degree : 2.
• Installation altitude : < 2000 m.
• Protection level : IP 30.
• Operating temperature: +5 to 45 °C.
• Input voltage : 220-400 VAC (198 to 440 Volts), 50-60 Hz.
• Mains input : Dual spring terminal blocks for 1,5 mm² (AWG 16) wire.
• Power consumption : 360 W max.
• Power factor : 0,99 (built with PFC).
• Dielectric strength : 4000 VAC between input and output.
2500 VAC from input to chassis.
• Presentation : galvanized steel case and front panel with epoxy finish.
• Mounting : Integral symmetrical DIN rail clips.
Paralleling
• Load share controller (1 wire) on dual spring terminal blocks for 1,5 mm² wire (AWG 16).