Description
Voltage
• Floating outputs on spring terminal block with levers.
• Max wire cross sectional area : 2.5mm² (AWG 12).
• Output voltage : 24 V DC (according to EN 61131-2)
• Ripple : < 5%
• Hold up time : 20 ms at nominal voltage and current
• Indicator : green power-on LED indicator.
Current
• Max I : 2,5A
Current / Voltage / Ripple
0 A 28,3 V 0%
0,5 A 26,9 V 1%
1 A 26,0 V 2%
1,5 A 25,3 V 3%
2 A 24,6 V 4%
2,5 A 24,0 V 5%
Power
• Output power : 60 W.
Protection
• Short circuit protection by fuse in the secondary circuit
Other specifications
• Input voltage : 230/400 V ±15V AC single or two-phase 50/60 Hz.
• Mains input : spring terminal block with leveres.
• Max wire cross sectional area : 1.5 mm² (AWG 16).
• Screw type earth terminal : 2.5 mm² (AWG 12).
• Safety : Class I, complies with EN 61558-2-6.
• Protection level : IP 30.
• Output voltage complying with EN 61131-2 for automation systems.
• EMC : Complies with EN 61000-6-2 and EN 61000-6-4.
• Power consumption : 75 W max.
• Operating temperature : +5 to +55 °C.
• Dielectric strength : 4500 VAC from input to output,
2250 VAC from input to chassis.
500VAC from output to chassis.
• Presentation : galvanized steel case and front panel with epoxy finish.
Mounting
• Integral symmetrical DIN rail clips